QUATTRO

Inversor-cargador-victron-Energy-quattro-24/5000.jpg Inversor / Cargador Victron Energy Quattro
Inversor-cargador-Victron-Energy-quattro-2475000_1.jpg Inversor/Cargador Victron Energy Quattro
digital_multi.jpg Digital Multi

Two AC inputs with integrated transfer switch

The Quattro can be connected to two independent AC sources, for example the public grid and a generator, or two generators. The Quattro will automatically connect to the active source.

Two AC Outputs

The main output has no-break functionality. The Quattro takes over the supply to the connected loads in the event of a grid failure or when shore/generator power is disconnected. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.

The second output is live only when AC is available on one of the inputs of the Quattro. Loads that should not discharge the battery, like a water heater for example can be connected to this output.

Virtually unlimited power thanks to parallel operation

Up to 6 Quattro units can operate in parallel. Six units 48/10000/140, for example, will provide 54 kW / 60 kVA output power and 840 Amps charging capacity.

Three phase capability

Three units can be configured for three phase output. But that’s not all: up to 6 sets of three units can be parallel connected to provide 162 kW / 180 kVA inverter power and more than 2500 A charging capacity.

PowerControl – Dealing with limited generator, shoreside or grid power

The Quattro is a very powerful battery charger. It will therefore draw a lot of current from the generator or shoreside supply (16 A per 5 kVA Quattro at 230 VAC). A current limit can be set on each AC input. The Quattro will then take account of other AC loads and use whatever is spare for charging, thus preventing the generator or mains supply from being overloaded.

PowerAssist – Boosting shore or generator power

This feature takes the principle of PowerControl to a further dimension allowing the Quattro to supplement the capacity of the alternative source. Where peak power is so often required only for a limited period, the Quattro will make sure that insufficient mains or generator power is immediately compensated for by power from the battery. When the load reduces, the spare power is used to recharge the battery.

Solar energy: AC power available even during a grid failure

The Quattro can be used in off grid as well as grid connected PV and other alternative energy systems.
Loss of mains detection software is available.

System configuring

- In case of a stand-alone application, if settings have to be changed, this can be done in a matter of minutes with a DIP switch setting procedure.
- Parallel and three phase applications can be configured with VE.Bus Quick Configure and VE.Bus System Configurator software.
- Off grid, grid interactive and self-consumption applications, involving grid-tie inverters and/or MPPT Solar Chargers can be configured with Assistants (dedicated software for specific applications).

On-site Monitoring and control

Several options are available: Battery Monitor, Multi Control Panel, Ve.Net Blue Power panel, Color Control panel, smartphone or tablet (Bluetooth Smart), laptop or computer (USB or RS232).

Remote Monitoring and control

Victron Ethernet Remote, Victron Global Remote and the Color Control Panel.
Data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.

Remote configuring

When connected to the Ethernet, systems with a Color Control panel can be accessed and settings can be changed.

Specifications

 

12/3000/120 - 50/50

24/3000/70 - 50/50

12/5000/220 - 100/100

24/5000/120 - 100/100

48/5000/70 - 100/100

24/8000/200-100/100

48/8000/110-100/100

48/10000/140-100/100
Electrical specifications        
PowerControl Yes Yes Yes Yes
PowerAssist Yes Yes Yes Yes
Transfer switch 2 x 50 Amp 2 x 100 Amp 2 x 100 Amp 2 x 100 Amp
Parallel and 3-phase operation Yes Yes Yes Yes
Inverter        
Output power (continuous) (3) 3000 VA 5000 VA 8000 VA 10000 VA
Output power 25 ºC 2500 W 4500 W 7000 W 9000 W
Output power 40 ºC 2200 W 4000 W 6300 W 8000 W
Output Power 40 ºC 6000 W 10000 W 16000 W 20000 W
Output voltage (1) 230 Vac ±2%
Output Frequancy 50 Hz ±0,1 Hz
Wave Signal Senoidal verdadera
Maximum efficiency 93 / 94 % 94 / 94 / 95 % 94 / 96 % 96 %
Zero load power 15 / 15 W 25 / 25 / 25 W 30 / 35 W 35 W
Zero load power (AES mode) 10 / 10 W 20 / 20 / 20 W 25 / 30 W 30 W
Charger        
Input voltage 187 - 265 Vac, 45 - 65 Hz, Power factor 1
Charge current 120 / 70 Amp 220 / 120 / 70 Amp 200 / 110 Amp 140 Amp
Auxiliar Battery charge current 4 Amp (12 and 24 volts only)
Absroption charge voltage 14,4 / 28,8 Vcc 14,4 / 28,8 / 57,6 Vcc 28,8 / 57,6 Vcc 57,6 Vcc
Float charge voltage 13,8 / 27,6 Vcc 13,8 / 27,6 / 55,2 Vcc 27,6 / 55,2 Vcc 55,2 Vcc
Storage mode voltage 13,2 / 26,4 Vcc 13,2 / 26,4 / 52,8 Vcc 26,4 / 52,8 Vcc 52,8 Vcc
Battery temperature sensor Included
General        
Auxiliary output (A) (5) 25 50 50 50
Programmable relay (6) 3x
Protection (2) a - g
Operating temperature range -20 to 50 ºC
Mechanical specifications        
Device mounting Wall mount (backplate included).
Battery connections Four M8 bolts (2 plus and 2 minus connections)
Battery connections Screw terminals 13 mm2 (6 AWG) Bolts M6
Inverter Dimensions (mm) 362 x 258 x 218

470 x 350 x 280

444 x 328 x 240

444 x 328 x 240

470 x 350 x 280 470 x 350 x 280
Weight 19 Kgr 34 / 30 / 30 Kgr 45 / 41 Kgr 45 Kgr
Environmental specifications        
IP Degree of protection IP 21
Operating temperature range - 25 to 50 ºC
Warranty 5 years
Standards  
Safety EN-IEC-60335-1, EN-IEC 60335-2-29, IEC 62109-1
Emission, Immunity EN55014-1, EN 55014-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-2, EN 61000-6-1
Automotive Directive 2004/104/EC


1) Can be adjusted to 60 HZ; 120 V 60 Hz on request
2) Protection key:
     a) output short circuit
     b) overload
     c) battery voltage too high
     d) battery voltage too low
     e) temperature too high
     f) 230 VAC on inverter output
     g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25˚C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm,
     DC under voltage or genset start/stop function
     AC rating: 230 V / 4 A